Product Description

Function and Description of Deflagration Type in Line

The PRECON ® 20502 in-line deflagration flame arrester provides protection against confined deflagration in enclosed pipe line. When installing the deflagration flame arrester, make sure that the distance between potential ignition sources and the location of the installed Flame Arrester , does not exceed the Lu/D ratio ( pipe length/pipe diameter), for which the device was tested. The installation of the deflagration flame arrester into horizontal and vertical pipes is permissible.The deflagration flame arrester is symmetrical and offers bidirectional flame transmission protection.

The Flame Arrester consists of two housing parts and the PRECON® flame arrester Element in the center. The PRECON® flame arrester unit consists of multiple layers of Flame Arrester element and spacers assembled in an arrester (Element) housing.  The number of Flame Arrester element and Flame Quenching Diameter depends on the size of Flame Arrester and the Explosion Group.The design can be used with Operating Pressure range up to 1.1bara, operating temperature range up to + 60°C.Type-approved in accordance with the ATEX Directive and EN ISO 16852 for Explosion group IIB3/IIC.

The PRECON 20502 In-line deflagration flame arresters are also available with eccentric housing to drain condensate build up in the housing. Due to its eccentric design the device can be installed in pipelines that close to floors or walls and low points, where condensate can collect within the piping system, can be avoided. When installing the deflagration
 
Special Features and Advantages :-

  • Sizes available from 1/2” NB to 12” NB.
  •  Eccentric design prevents condensate build up.
  •  Flame Arrester Element can be cleaned easily.
  •  Low Pressure drop.
  •  Bi-directional flame transmission proof design.
  •  Protects against deflagrations for all explosion groups IIA,IIB3 and IIC
  •  Easily replaceable and Cost effective spare parts.

Technical Details of InLine Deflagration Flame Arresters

Selection of Material :-

Description

A

B

C

Body

CS/A 216 Gr WCB

A 351 Gr CF8/SS304

A 351 Gr CF8M/SS316

Shell

A 106 Gr B

SS 304

SS 316

Flame Element

SS 316/SS 316L

SS316/SS 316L

SS316/SS 316L

Gasket

NAM 39

PTFE

PTFE

Fasteners

C/S zinc plated

SS 304

SS 304

 Explosion Group :-

MESG

Explosion Group ( IEC)

>0.9 mm

IIA

≥ 0.65 mm

IIB3

<0.5 mm

IIC

 Size

15 mm

20 mm

25

mm

40

mm

50

mm

65

mm

80

mm

100

 mm

150 mm

200 mm

250 mm

300 mm

 End connection :-

BS 10 Table D,E,F

BS

DIN PN 6, PN 10, PN 16

DIN

ANSI 150 FF/RF, 300 RF

ANSI

DETAIL OF ATEX CERTIFICATE

Size

Lu/D

Explosion Group

ATEX Certificate Number

 

15 mm NB to  150 mm NB

50

IIA/IIB3

IBExU15ATEX2158 X

200 mm NB to 300 mm NB

30

IIA/IIB3

IBExU15ATEX2158 X

50 mm NB to 300 mm NB 

30

IIC

IBExU letter No: 5347/16 certificate awaited

 